- Hãng sản xuất: Sonel

- Model: MRP-201

- Nước sản xuất: Ba Lan

Testing RCD breakers of AC, A and B types.
- testing of general, short delay and selective RCDs for the rated current values In =10, 30, 100, 300 and 500 mA,
- simultaneous measurement of tripping current IA and disconnection time tA, for currents 0,5In, 1In, 2In , 5In
- ability to measure touch voltage UB and earth resistance RE without tripping,
- AUTO RCD test function.

  • AC voltage and frequency measurement.
  • PE lead connection check using a touch electrode.
  • Bulit-in memory for up to 990 cels of measurement results.
  • Wireless radio communication interface.

Professional software for reading data and creating reports.

 RCD trigger test and response time measurement tA 

Measurement range according to IEC 61557: 0ms...the upper limit of the displayed value

RCD type Rated Current
Multiplication
Factor
Range Resolution Accuracy
General 
or short delay
0,5*IΔn 0...300ms

1 ms


±(2% m.v. + 2 digits)*
1*IΔn
2*IΔn 0...150ms
5*IΔn 0...40ms 
Selective 0,5*IΔn 0...500ms
1*IΔn
2*IΔn 0...200ms
5*IΔn 0...150ms

*for IΔn= 10mA and 0,5 IΔn accuracy is ±2% m.v. + 3 digits

  • residual current setting accuracy:
    - for 1*IΔn, 2*IΔn and 5*IΔn: 0...8%,
    - for 0,5*IΔn : -8...0%,
  • nominal voltage Un: 220V, 230V, 240V,
  • work voltage range: 180...270V,
  • nominal frequency fn: 50Hz, 60Hz,
  • work frequency range: 45Hz...65Hz.

RCD disconnecting current measurement for a sine AC test current (IA)

Measurement range according to IEC 61557: (0,3...1,0)IΔn

Selected
rated RCD
current
Range Resolution

Measurement 
current

Accuracy
10mA 3,3...10,0mA 0,1mA 0,3mA x IΔn
...1,0mA x IΔn
±5% IΔn
30mA 9,0...30,0mA
100mA 33...100mA 1mA
300mA 90...300mA
500mA 150...500mA
  • start of measurement from the positive or negative half sine period of the test current
  • test current flow time - max. 7510ms at f=50,0Hz.

RCD disconnecting current measurement for unidirectional pulsed residual current and unidirectional pulsed current with a 6mA DC offset (IA)

Measurement range according to IEC61557: (0,15...1,4) IΔn for IΔn > 30mA and (0,15...2)IΔn for IΔn=10mA

Selected
rated RCD
current
Range Resolution

Measurement 
current

Accuracy
10mA 1,5...20,0mA 0,1mA 0,15 x IΔn
...2,0mA x IΔn
±10% IΔn
30mA 4,5...42,0mA
100mA 15...140mA 1mA 0,15mA x IΔn
...1,4mA x IΔn
±10% IΔn
300mA 45...420mA
  • start of the measurement from the positive or negative half sine period of the test current
  • test current flow time - max. 14710ms at f=50Hz

 

RCD response time measurement for the residual DC current (IA)

Measurement range according to IEC61557: (0,2...2)IΔn

Selected
rated RCD
current
Range Resolution

Measurement 
current

Accuracy
10mA 2...20,0mA 0,1mA 0.2mA x IΔn
...2,0mA x IΔn 
±10% IΔn
30mA 6...60mA 1mA
100mA 20...200mA
300mA 60...600mA
  • measurement possible for positive or negative residual current
  • test current flow time - max. 4500ms at f=50Hz


IΔn - rated residual current value RCD


Touch voltage measurement referred to the rated residual current (UB)

Measurement range according to IEC61557: 10,0...99,9V

Range Resolution  Measurement current  Accuracy 
0...9,9V 0,1 0,4 x IΔn 0...10% IΔn m.v. ± 5 digits
10,0...99,9V 0...15% IΔn m.v.

Earthing resistance measurement (RE)

Selected
rated RCD
current
Range Resolution

Measurement 
current

Accuracy
10mA 0,01...5,00kΩ 0,01kΩ 4mA 0...+10% m.v. ± 5 digits
30mA 0,01...1,66kΩ 12mA 0...+10% m.v. ± 5 digits
100mA 1...5000Ω 40mA 0...+5%m.v. ± 5 digits
300mA 1...166Ω 120mA
500mA 1...100Ω 200mA

 



Voltage measurement
Measurement range in accordance with IEC 61557: 1,1Ω...1,99kΩ

Range Resolution

Accuracy

0,00...299,9V 0,1V ±(2% m.v. + 6 digits)
300...500V 1V ±(2% m.v. + 2 digits)
  • frequency range: 45...65Hz 
Range Resolution

Accuracy

45,0...65,0Hz 0,1Hz ±(0,1% m.v. + 1 digit)
  • voltage range 50...500V

Electric security:
- type of insulation: double, according to EN 61010-1 and IEC 61557
- measurement category: CAT IV 300V (III 600V) acc. to EN 61010-1
- protection class: IP67

Other technical data:
- power supply: alkaline batteries LR6 (AA) (4 pcs.)

Rated operational conditions:
- operating temperature: -10...+50°C
- storing temperature: -20...70°C
- humidity: 20...80%

„m.v.” - measured value.

Sản phẩm khác
← BACK
 
↑ TOP
Hỗ trợ trực tuyến
Giỏ hàng của bạn
Trang chủ Hướng dẫn đặt hàng Hướng dẫn thanh toán Vận chuyển và giao hàng Chính sách bảo hành Sơ đồ đường đi Tuyển dụng Liên hệ

SIÊU THỊ THIẾT BỊ ĐO QUANG MINH - CÔNG TY TNHH ĐẦU TƯ VÀ TT QUANG MINH
ĐT: 04.3873.0880 - Hotline: 090.400.3848 - Fax: 04.3873.0880
Email: kd@sieuthithietbido.com - Website: www.sieuthithietbido.com - www.sieuthithietbidienmay.net

Thiết bị đo RCD Sonel MRP 201, Thiết bị kiểm tra RCD Sonel Thiết bị đo RCD Sonel MRP 201, Thiết bị kiểm tra RCD Sonel By Siêu thị thiết bị điện máy Quang Minh: nhà cung cấp Thiết bị đo RCD Sonel MRP 201, Thiết bị kiểm tra RCD Sonel Chính hãng Giá rẻ nhất - Gọi ngay 04.3873.0880 - 090.400.3848 5 sao trên 1695 khách hàng bình chọn