Measurement of short circuit loop impedance (ZL-PE, ZL-N, ZL-L)
Measuring range according to IEC61557: 0,13…1999? for 1,2m test leads; 0,25…1999? for UNI-SCHUKO adapter
Range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(5% m.v. + 3 digits) |
20,0...199,9Ω | 0,1Ω | ±(4% m.v.. + 3 digits) |
200...1999Ω | 1Ω |
• rated operating voltage UnL-N/ UnL-L: 110/190V, 115/200V, 127/220V, 220/380V, 230/400V, 240/415V, 290/500V, 400/690V,
• operating voltage range: 100…440V (for ZL-PE and ZL-N) and 100…750V (for ZL-L)
• high current measurement (up to 30A),
• operating frequency range: 45…65Hz,
• control of correctness of PE terminal connection by means of a contact electrode (applicable to ZL-PE),
• measurement is also possible when L and N circuits are swapped,
• measurement of resistance and reactance components,
• short circuit current calculation.
Measurement of short circuit loop impedance ZL-PE RCD (without RCD tripping)
Measuring range according to IEC61557: 0,43...1999? for 1,2m test leads; 0,50...1999? for UNI-SCHUKO adapter
Range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(6% m.v. + 10 digits) |
20,0...199,9Ω | 0,1Ω | ±(6% m.v. + 5 digits) |
200...1999Ω | 1Ω |
• operating voltage range: 100 ... 440V,
• rated operating voltage Un: 110V, 115V, 127V, 220V, 230V, 240V, 390V, 400V,
• control of correctness of PE terminal connection by means of a contact electrode,
• measurement is also possible when L and N circuits are swapped,
• measurement of resistance and reactance components,
• short circuit current calculation.
Range | Resolution | Accuracy |
0,0V...249,9V | 0,1V | ±(2% m.v. + 4 digits) |
250V...750V | 1V | ±(2% m.v. + 2 digits) |
• measurement available for all settings of short-circuit loop (ZL-PE, ZL-PE RCD and ZL-N,L-L),
• frequency range 45…65Hz,
• overvoltage alarm.
Electrical safety:
- type of insulation: double, according to IEC 61010-1
- measurement category: CAT IV 600V (CAT III 1000V)
- protection class acc. to EN 60529: IP54
Other technical data
- power supply: alkaline batteries or NiMH rechargeable batteries, size AA (4 pcs)
- number of Z measurements (for alkaline batteries): >3000 (2 measurements per minute)
- time to Auto-OFF: 120 seconds
- data transmission: USB
- memory of measurement results: 990 cells, 3500 entries
- display: LCD segment
- dimensions: 260x190x60mm
- meter weight: ca. 2,2 kg
Rated operational conditions:
- operating temperature: 0...+45°C
- storage temperature: -20...60°C
- humidity 20-80%
The instrument meets the requirements of EMC standards
Download:
SIÊU THỊ THIẾT BỊ ĐO QUANG MINH - CÔNG TY TNHH ĐẦU TƯ VÀ TT QUANG MINH
ĐT: 04.3873.0880 - Hotline: 090.400.3848 - Fax: 04.3873.0880
Email: kd@sieuthithietbido.com - Website: www.sieuthithietbido.com - www.sieuthithietbidienmay.net