- Measurement of very low short circuit loop impedances (with resolution 0,1mΩ) with a current of 150A at 230V; maximum 280A at 440V or measurement with a current of 23A at 230V; maximum 42A at 440V.
- measurements in installations with rated voltages between: 220/380V and 230/400V and frequencies 45...65Hz,
- ability to perform measurements in short circuit system: phase-phase, phase-protective, phase-neutral,
- differentiation between the phase voltage and the inter-phase voltage while calculating the shortcircuit current,
- Ability to change the length of test leads (measurement 23/42A),
- four-pole method, test leads do not require calibration (measurement 150/280A).
- Touch voltage and touch shock voltage measurement (with resistor 1kΩ).
- AC voltage measurement in range 0...440V.
- Memory for 999 measurement results with an ability to transfer the data to a PC.
- Meter meets the requirements of the standard EN 61557.
Electric security:
- type of insulation: double, according to EN 61010-1 and IEC 61557
- measurement category: CAT IV 300V acc. to EN 61010-1
- protection class acc. to EN 60529: IP20
Other technical data:
- power supply alkaline batteries LR14 (C) (5 pcs.)
- resistor limiting the current:
for measurement 4p: 1,5Ω
for measurement 2p: 10Ω
- number of short circuit loop measurements (alkaline batteries): min. 2000 (4/min.)
- temperature coefficient: ±0,1% of measured value /°C
Rated operational conditions:
- operating temperature: 0...+40°C
Voltages measurement (True RMS)
Range |
Resolution |
Accuracy |
0...440V |
1V |
±(2% m.v. + 2 digits) |
· frequency range: DC, 45...65Hz
· input impedance of the voltmeter: >200kΩ
Frequency measurement (for voltages within the range 50...440V)
Range |
Resolution |
Accuracy |
45,0...65,0Hz |
0,1Hz |
±(0,1% m.v. + 1 digits) |
Short circuit loop parameters measurement using high current (4p, Imax=280A)
High-current of measurement of short circuit loop impedance ZS:
measuring range according to IEC61557: 7,2mΩ...1999mΩ
Range |
Resolution |
Accuracy |
0...199,9mΩ |
0,1mΩ |
±(2% m.v. + 2mΩ) |
200...1999mΩ |
1mΩ |
Short circuit resistance RS and reactance XS display range
Range |
Resolution |
Accuracy |
0...199,9mΩ |
0,1mΩ |
±(2% m.v. + 2mΩ)
impedance reading for
a particular measurement |
200...1999mΩ |
1mΩ |
Prospective short circuit loop current
measuring range according to IEC 61557:
for Un = 230V 115,0A...32,0kA
for Un = 400V 200A...55,7kA
Range |
Resolution |
Accuracy |
115,0...199,9A |
0,1A |
accuracy of the current
indication computed,
respectively,
with the use of resistance
measurement |
200...1999A |
1A |
2,00...19,99kA |
0,01kA |
20,0...199,9kA |
0,1kA |
200kA...* |
1kA |
* 230 kA for UL-N
400 kA for UL-L
Measurement of short circuit loop using standard current (2p, Imax=42A)
Touch voltage measurement UST (shock voltage UT)
Range |
Resolution |
Accuracy |
0...100V |
1V |
±(10% m.v. + 2 digits) |
Short circuit loop impedance ZS measurement:
measuring range according to IEC61557: 0,13Ω...199,9Ω for 1,2m long test leads
Range |
Resolution |
Accuracy |
0,00...19,99Ω |
0,01Ω |
±(2% m.v. + 3 digits) |
20,0...199,9Ω |
0,1Ω |
±(3% m.v. + 3 digits) |
Short circuit resistance RS and reactance XS display range
Range |
Resolution |
Accuracy |
0,00...19,99Ω |
0,01Ω |
±(2% m.v. + 3 digits)
impedance reading for
a particular measurement |
20,0...199,9Ω |
0,1Ω |
±(2% m.v. + 3 digits)
impedance reading for
a particular measurement |
Prospective short circuit loop current
Range |
Resolution |
Accuracy |
1,150...1,999A |
0,001A |
accuracy of the current
indication computed,
respectively,
with the use of resistance
measurement |
2,00...19,99A |
0,01A |
20,0...199,9A |
0,1A |
200...1999A |
1A |
2,00...19,99kA |
0,01kA |
20,0...40,0kA |
0,1kA |
„m.v.” - measured value